Terminals and Connections for Three-Phase Motors-Single Speed---6 Lead
NEMA  - 6 Leads
Single Voltage
External WYE Connection
L1
3
2
L3
L2
1
4+5+6
JOIN
Single Voltage
External Delta Connection
L1
L2
L3
1+6
3+5
2+4
NEMA  - 6 Leads
Single and Dual Voltage  WYE-DELTA Connections----6 Lead
Single Voltage
Start  (Wye)
L1
L2
L3
1
2
3
4+5+6
JOIN
Run (Delta)
1+6
2+4
3+5
-----
 
 
 
Dual Voltage Based on 1.732/1
Terminals and Connections for Three-Phase Motors-Single Speed---9 Lead
JOIN
L3
L2
L1
High  (Wye)
1
2
3
4+5+6
Low  (Delta)
1+6
2+4
3+5
-----
Voltage
JOIN
L3
L2
L1
High 
1
2
3
4+7,, 5+8,, 6+9
Low 
1+7
2+8
3+9
4+5+6
Voltage
JOIN
L3
L2
L1
High
1
2
3
4+7,, 5+8,, 6+9
Low 
1+6+7
2+4+8
3+9+5
4+5+6
Voltage
Three phase Connections 3 ph  Motors-Single Speed --- 12
JOIN
L3
L2
L1
High 
1
2
3
4+7,, 5+8.. 6+9,, 10+11+12
Low 
1+7
2+8
3+9
4+5+6,, 10+11+12
Voltage
Dual Voltage  External WYE Connection
Dual Voltage
WYE-Connected Start-----DELTA-Connected Run
 
 
 
JOIN
L3
L2
L1
Wye
1
2
3
4+7,, 5+8.. 6+9,, 10+11+12
Delta
1+12
2+10
3+11
4+7,, 5+8,, 6+9
Connect
High voltage
Dual Voltage
WYE-Connected Start-----DELTA-Connected Run
Low voltage
JOIN
L3
L2
L1
Wye
1+7
2+8
3+9
4+5+6,,  10+11+12
Delta
1+6+7+12
2+4+8+10
3+5+9+11
----------------
Connect
Three phase Connections 3 ph Motors-Single Speed
IEC (European) 6 Leads
Single and Dual Voltage WYE-DELTA Connections

Single Voltage
Dual Voltage Based on 1.732 : 1
JOIN
T(L3)
S(L2)
R(L1)
Start  (Wye)
U1
V1
W1
U2+V2+W2
Run  (Delta)
U1+W2
V1+U2
W1+V2
-----
 
(Wye)
Low   (Delta)
U1
U1+W2
V1
V1+U2
W1
U2+V2+W2
W1+V2
-----
JOIN
R(L1)
S(L2)
T(L3)
Dual Voltage   IEC (European) 12 Leads
WYE-Connected Start DELTA-Connected Run
High  (Wye)
Voltage
(Delta)
R(L1)
S(L2)
T(L3)
JOIN
U1
V1
W1
U1+W6
V1+U6
W1+V6
U2+U5,, V2+V5.. W2+W5,, U6+V6+W6
U2+U5,, V2+V5.. W2+W5,, U6+V6+W6
High voltage
Connect
Connect
Low Voltage
(Wye)
(Delta)
Connect
R(L1)
S(L2)
T(L3)
JOIN
U2+V2+W2,, U6+V6+W6
-------------
U1+U5
U1+U5+W2+W6
V1+V5+U2+U6
W1+W5+V2+V6
V1+V5
W1+W5
Sample European Connection
By Les McWatters