When you get a call for a transformer Here is what you need to know: 1 What is the voltage of this load? 2 Is the load single-phase or three-phase? 3 What is the power requirement for this load? We have to find a KVA value. If only amps are known, use the full load chart or the following formulas. Single phase "KVA"= Volts (loads) x Amps (load) 1000 Three phase "KVA" = Volts (load) x Amps (loads) x 1.732 1000 (Square root of 3 = 1.732) 4 What is the frequency? 5 What is the supply or source voltage? Are primary taps required? 6 Is there a special temp or insulation ? If not, use standard general purpose transformers 7 Is the transformer to be installed indoors or outdoors? With the above information you should be able to select a transformer. Note: Other things that may require special units may include, copper windings; low temperature rise units; units for applications in ambient temperatures higher than 40 deg C; units to be used at a high altitude above 3300 feet; special impedances; and many others. If requirements arise that do not fit the description of standard units, contact your dealer. Calculation Examples: What is the proper transformer to supply an 3 Phase electric heater rated 100 amps, at 240 volts, 60 Hz? The supply voltage is 480 volts, three-phase, 60 Hz. The transformer is installed indoors. 150 C with standard taps is required. Solution: You have all the information with the exception of the load KVA. We know that: Three-phase KVA = Volts (load) x Amps (load) x 3 = 240 x 100 x 1.732 = 41.6 1000 1000 A 480 volt to 240 volt (Delta-Delta), three-phase, 45 KVA (which is the next standard KVA rating) general purpose transformer is needed. Example: You have a motor load of 160 amps at 480 volts 3 phase and a supply voltage of 600 volts 3 phase. Step 1- 160 Amps x 480 Volts x "square root of 3" = 133 KVA Step 2- The next bigger size is 150KVA therefore Step 4- 150KVA divided by "root 3",then divided by 600 V= 144 A Primary Step 5- 150KVA divided by "root 3", then divided by 480V= 180 A Secondary Step 6- Secondary conductor size =180A*1.25=225A or 4/0 Step 7- Primary Breaker=144A*1.25=180A Note- CEC Rule 26-256(3) says you need next size larger so: 200A The following must be known before a transformer can be selected: KVA --The rating or capacity of the transformer Frequency-- Usually 60 Hz. Primary Voltage-- Designates the voltage for which the primary winding is designated. Phase-- Load requirements (single-phase or three-phase) If the load is three-phase, both the supply and the transformer must be three-phase. If the load is single-phase, the supply can be either single or three-phase, but the transformer must be single-phase. Secondary Voltage-- Designates the load voltage for which the secondary winding is designed. Taps-- Adjustment capability for voltage variations. Location of Installation-- Indoor or Outdoor Other Considerations-- Mounting Requirements, Sound Levels, Impedance, Special Applications, K-Rating, Copper Windings, Electrostatic Shields, Temperature Rise, Insulation Class |
By Cody McWatters |
Transformer Calculations |

